Usage
Remote monitoring and advanced analysis of power grids and surge arresters above 1 kV
Measurements and perception
Resistive component from 0 to 3 mA (± 10%)
Arrester measurement standard: IEC 60099-5
Detection: failure, fire, voltage, counter counter, device temperature, ambient temperature, slope, location
Measuring cycle: 1 hour
Work environment
Frequency range: 48 to 62 Hz
Temperature range: -40 ° C from + 85 ° C
Housing and assembly
Ingress protection: IP 67
Housing material: Thermoplastic V-0 (UL 94), stainless steel A2 or A4
Communications
Bluetooth, 4G/5G or LoRaWAN
Communication cycle:
– In real time – all significant errors (fire, destruction of the arrester, exceeding the recommended measurements),
– Once a day – UDP package; for other measurements (with default settings),
– Once every seven days – MQTT package; for other measurements (with default settings).
Before delivery check
4G and 5G mobile network:
• the presence of a mobile network signal at a standstill and,
• eligibility for data transfer with the mobile operator.
Installation guide
Read the user manual carefully before starting the installation.
It can be found on the back side of the packaging. The RAM-1 device must be installed on the grounding side of the surge arrester. There must not be a direct connection between the grounding side of the surge arrester and the RAM-1 device without and intermediate grounding. The metal plate of the RAM-1 device must be turned towards the grounding point. If the device is installed incorrectly it will not work properly. The installation guide for the installation on poles/towers are not necessary. The device must be installed in the top third of the pole/tower.
Installation guideSUPER FEATURES
READ MORE20 years on a battery from -40 to +85 degrees Celsiu, 250 kB of data per month for standard configuration with UDP and MQTT packages.
CLOUD CONNECTIVITY
READ MORERemote monitoring and advances analysis of electricity transmission and distribution networks.
TECHNICAL DATA
READ MOREMeasurement of resistive component of leakage current of surge arrester, Surge counter, ambient temperature and temperature of device.